PROLOGIC
PLDAIO
The PMDAIO module is a multipurpose combination ofinputs and outputs. The
module can accommodate either 2 or 3 wire RTD sensors, current (0-20mA) and
voltage (0-10V) inputs, current (0-20mA) or voltage (0-10V) output, and digital
inputs and outputs.

RTD INPUTS:

There are 2 RTD inputs on the module. The RTD resistance is read by the
module circuitry, linearised and converted to degrees Centigrade. No ranging is
required as the module covers the full range of the RTD as indicated in the RTD
table. The value that is read from the Modbus register is the actual temperature in
degrees centigrade to 0.1°C resolution. ie: a value of 3451 corresponds to a
temperature of 345.1°C. The RTD type is setup by writing a value to the RTD Type
register. The value is obtained from the table below. For example to select a
PT100 RTD, the value "1" must be written to the RTD Type register. A value of
-32767 is used to indicate downscale burnout.
Note: As there is no inter-channel isolation, isolated RTD's must be used in order to prevent ground loops and
reading errors.

ANALOG INPUTS:

The Analog Inputs (2) can be configured by internal jumpers as either a current input (0- 20mA) or a voltage
input (0-10V). An input of 0 - 20mA input current or 0 – 10V input voltage represents an output value of 0 - 4095
(12 bits) in the corresponding Modbus register.

ANALOG OUTPUT:

There is a single analog output which can be configured with internal jumpers for a current output (0-20mA) or
voltage output (0-10V). The resolution is 12 bits, so writing a value to the Modbus register for each output of
0 - 4095 would give an output current of 0 - 20mA. A value of 819 ± 1LSB will give a current output of 4mA.

DIGITAL INPUTS:

There are 4 digital inputs on the module. The inputs share a common terminal and can be configured for
common positive or common negative. The inputs have got counters associated with them. The counters
operate in three modes
.
In mode 0 all the counters are disabled.

In mode 1 all counters are 32 bit counters allowing a count value from 0 to 4294967295. The count value can
be cleared by writing a zero to the associated registers or preset to any other value using the same method.

In mode 2 the inputs are connected as up/down counters. Input 1 will increment counter 1 whilst input 2
decrements counter1.

Note: The count values are not battery backed-up and will be lost if power is turned off. The format of the
registers allows the status of the inputs to be read as either single bits or all at once as a single register on
the Modbus network.

DIGITAL OUTPUTS:

The module has 2 open collector (NPN) digital outputs. The outputs may be used to drive lamps or external
relays when more drive capability is required. The outputs are written to by the Modbus master device such as
a PC or PLC. Each output can be individually switched on or off, or all outputs can be set up at the same time
by writing a single number to the output register which represents the status of all outputs. An output watchdog
timer can be configured to switch off all the outputs if there has been no communications with the module for
up to 255 seconds. A value of 0 seconds will disable this timer and the outputs will remain in the last
programmed state.